Solar-panel sizing formula
array watts = daily Wh ÷ peak sun hours ÷ (efficiency % / 100)Use seasonal peak-sun-hour data for the travel area and month. Flat panels, roof vents, antennas, trees, and nearby vehicles can reduce real output.
Estimate the solar-array wattage needed to replace an RV or off-grid system’s average daily electrical use.
Peak sun hours are not daylight hours; they represent equivalent hours at full rated solar output.
array watts = daily Wh ÷ peak sun hours ÷ (efficiency % / 100)Use seasonal peak-sun-hour data for the travel area and month. Flat panels, roof vents, antennas, trees, and nearby vehicles can reduce real output.
Controller amp rating alone is insufficient. Check maximum photovoltaic open-circuit voltage, cold-weather voltage rise, series/parallel layout, battery charge settings, and conductor protection.
Return to the solar, battery & RV planning workflow
For 1,200 Wh/day, four peak sun hours, and 70% overall efficiency, the minimum array is 428.6 W. With 200 W panels, round up to three panels: 600 W and an estimated 1,680 Wh/day. Check their actual dimensions against usable roof space.
extra array W = stored deficit Wh ÷ recovery days ÷ peak sun hours ÷ storage efficiency fractionFor charge-level mode, stored deficit Wh = nominal bank V × bank Ah × (target SOC% − starting SOC%) ÷ 100. A 12.8 V, 250 Ah bank going from 40% to 90% needs approximately 1,600 Wh restored. Do not apply depth of discharge or discharge efficiency again. Add this to the daily-load array requirement before rounding up to whole panels. For 1,200 Wh/day, four sun hours, and 70% load efficiency, daily use requires 428.6 W. Restoring 1,600 stored Wh in two productive days at 80% storage efficiency adds 250 W. The 678.6 W total rounds to four 200 W panels. After daily use, their surplus stores about 1,188.6 Wh/day, suggesting 1.35 productive days before charge-rate or taper limits.
No. They express the daily solar resource as equivalent hours at full reference irradiance. Use local, seasonal data for the travel month; four hours is an example, not a US-wide guarantee.
Choose missing stored energy or enter whole-bank capacity and starting/target state of charge in the optional recovery section. The tool adds enough generation to restore it over the selected productive days while covering daily appliance use. Recovery has a separate panel-to-storage efficiency, so do not add the same deficit to daily energy.
No. The displayed 25% current allowance is only a screening assumption, not a code requirement or final controller selection. Check photovoltaic voltage, short-circuit current, cold-weather limits, output limits, and manufacturer sizing instructions.